Application
NYY cables are an economical way of transmitting power
and control where armouring is not required. Used both indoor and outside
these cables are suitable for direct burial or through ducts, regulations
permitting. Availability is generally excellent with most sizes available
for shipping within a few days. |
|
Cable Construction
Plain copper wire conductors to VDE 0295 class 1 or
2, PVC insulation, bedding compound, PVC sheath – Black.
NYY can be supplied with a green/yellow earth conductor - reference
NYY-J or without an earth conductor – reference NYY-O.
|
|
Core Identification
| |
NYY-J |
NYY-O |
| Single Core |
Green/yellow |
Black |
| 2 Core |
- |
Brown, blue |
| 3 Core |
Brown, blue, G/Y |
Brown, black, grey |
| 4 Core |
Brown, black, grey, G/Y |
Brown, black, grey, blue |
| 5 Core |
Brown, black, grey, blue, G/Y |
Black, blue, brown, grey, black |
| 7 Core and above |
Black numbered cores, G/Y |
Black numbered cores |
| |
|
|
Technical Information
| Voltage rating |
0.6/1kV |
| Test Voltage |
4000V |
| Conductors |
VDE 0295 class 1 or 2 |
| |
(Conductors can be circular or sectional) |
| Temperature rating |
-30° to +70°C static |
| |
-5°C to +50°C for installation |
| Bending radius (static) |
1.5mm² to 16mm²: 6
x overall diameter |
| Single core |
15 x overall diameter static |
| Multi core |
12 x overall diameter static |
| Flame retardant |
VDE 0472 test B and IEC60332-1 |
| Design |
VDE 0276 IEC60502-1 |
| Also available with a screen
- type NYCY/NYCWY |
|