Niltox LF-319 Flexible Multi-core

Developed to meet the need for Low Smoke Halogen Free control cables. The Niltox LF-319 range covers all the popular sizes. Applications include airports, hospitals, lift shafts, heating and ventilating controls, in fact anywhere that conventional PVC YY cables were previously used. In addition to its LSHF properties these cables also offer a high degree of flame retardance therefore reducing the risks of speading fire. For screened versions please refer to Niltox LF-329 Screened Control.
    

Cable Construction

Fine copper wire strands to BS6360 class 5, Low Smoke Halogen Free insulation, black with white number coding, a green/yellow earth core is included in cables with more than two cores, grey Low Smoke Halogen Free outer sheath.

Technical Information

Voltage Working : 300/500V Test : 2000V
Temperature Range Flexing : -15°C to +70°C Static : -35°C to +70°C
Bending Radius Flexing : 15 x cable diameter Static 7.5 x cable diameter
Current Rating Refer to IEE Regs Table 4H3A&B
Conductor Stranding BS 6360 Class 5 & IEC60228 Class 5
Flame Retardance IEC 60332-3-24 Cat C. Independently tested by BRE
Halogen Free IEC 60754-1 & 2  
Low Smoke IEC 61034-1 & 2
 
Core ID Black numbered cores with a green/yellow earth core included in cables with more than 2 cores.

Technical Data

Part No.
Cores
& mm²
Weight
Kg/Km
O/D
mm
 31900702   2 x 0.75   40   5.1 
 31900703   3 x 0.75   46   5.1 
 31900704   4 x 0.75   58   5.4 
 31900705   5 x 0.75   72   6.0 
 31900707   7 x 0.75   91   7.1 
 31900712   12 x 0.75   121   9.1 
 31900718   18 x 0.75   198   10.2 
 31900725   25 x 0.75   227   12.2 
           
 31901002   2 x 1.0   45   5.3 
 31901003   3 x 1.0   52   5.6 
 31901004   4 x 1.0   62   6.1 
 31901005   5 x 1.0   73   6.5 
 31901007   7 x 1.0   96   6.9 
 31901012   12 x 1.0   147   9.2 
 31901018   18 x 1.0   221   10.8 
 31901025   25 x 1.0   356   12.8 
           
 31901502   2 x 1.5   54   5.9 
 31901503   3 x 1.5   79   6.3 
 31901504   4 x 1.5   89   7.2 
 31901505   5 x 1.5   99   7.9 
 31901507   7 x 1.5   132   7.9 
 31901512   12 x 1.5   196   10.4 
 31901518   18 x 1.5   299   12.6 
 31901525   25 x 1.5   410   15.1 
Part No.
Cores
& mm²
Weight
Kg/Km
O/D
mm
 31902502   2 x 2.5   88   7.3 
 31902503   3 x 2.5   104   7.5 
 31902504   4 x 2.5   127   8.0 
 31902505   5 x 2.5   151   8.7 
 31902507   7 x 2.5   201   10.2 
 31902512   12 x 2.5   318   12.7 
 31902518   18 x 2.5   510   16.2 
           
 31904003   3 x 4.0   153   8.8 
 31904004   4 x 4.0   191   9.3 
 31904005   5 x 4.0   232   10.4 
           
 31906003   3 x 6.0   228   10.6 
 31906004   4 x 6.0   264   10.9 
 31906005   5 x 6.0   332   12.0 
           
 31910004   4 x 10   455   13.8 
 31910005   5 x 10   531   14.8 
           
 31916004   4 x 16   692   16.4 
 31916005   5 x 16   913   18.8 
           
 31925004   4 x 25   1054   20.3 
 31925005   5 x 25   1306   22.6 
           
 31935004   4 x 35   1448   23.1 
 31935005   5 x 35   2018   26.8 
Other sizes are available on short
lead times, please tell us what you need

At FSC we refer to LSHF as Low Smoke Halogen Free

This term is interchangeable with LSZH (Low Smoke Zero Halogen), LSOH (Low Smoke Zero Halogen), OHLS (Zero Halogen Low Smoke) and FRNC (Flame Retardant Non-Corrosive). Beware of the terms LSF (Low Smoke and Fume) or RP (Reduced Propogation), when relating to signal or control cables will normally be modified PVC and produce 'Loads of Smoke and Fume'!

Fire retardant, fire resistant, flame resistant or flame retardant?

These terms are often misunderstood. Most cables when exposed to fire will not carry on functioning. If you require cable to continue working in the event of fire, and in accordance with various standards please call us.
Back to last page Return to TOP
Your browser does not support CSS. If images appear below, please disregard them.