BS8434 : 2 Enhanced Grade Fire Alarm Cables

The Enhanced grade of fire alarm cables are suitable for installations where evacuation may be delayed, for example hospitals, tunnels, and high rise buildings. Enhanced soft skin fire alarm cables are able to compete with traditional MICC (Mineral Insulated Copper Clad) in fire performance whilst reducing installation time and costs.

  We are able to offer many brands including Draka Firetuf Plus, IDH Kilflam 3000, Prysmian ( Pirelli ) FP Plus & Nexans Alsecure NX 200 Plus. Just specify when you call for a quote.

Construction

Plain copper conductor, circuit integrity low smoke halogen free insulation, metallic barrier tape with copper earth-wire maintaining longitudinal contact. Low Smoke Halogen Free sheath.

Technical Information

Conductors Copper wire Class 1 to BS6360 for sections 1.0 & 1.5 mm²
Copper wire Class 2 to BS6360 for sections 2.5 & 4.0 mm²
Voltage 300V/500V
Resistance to Fire Alone IEC 60331 : 3 hours at 750°C
BS6387 Cat. C: 3 hours at 950°C
Resistance to Fire with Water BS6387 Cat. W: 15 mins at 650°C
Plus 15 mins with water spray
Resistance to Fire with
Mechanical Shock
BS6387 Cat. Z: 15 mins at 950°C
Approvals BS8434-2 2003 BS5839 : 1 2002
BS EN 50200 PH120, BS7629, LPCB

Technical Data

Part No.
Cores
& mm²
Weight
Kg/Km
O/D
mm
 387E01002   2E 1.0   116   8.5 
 387E01003   3E 1.0   129   9.4 
 387E01004   4E 1.0   157   10.2 
 387E01502   2E 1.5   132   9.4 
 387E01503   3E 1.5   167   9.5 
 387E01504   4E 1.5   157   11.0 
 387E02502   2E 2.5   189   10.7 
 387E02503   3E 2.5   226   11.0 
 387E02504   4E 2.5   272   13.2 
 387E04002   2E 4.0   270   11.0 

* W on the end of the part number changes the sheath colour from red to white,
B changes the sheath colour to black.

 

At FSC we refer to LSHF as Low Smoke Halogen Free

This term is interchangeable with LSZH (Low Smoke Zero Halogen), LSOH (Low Smoke Zero Halogen), OHLS (Zero Halogen Low Smoke) and FRNC (Flame Retardant Non-Corrosive). Beware of the terms LSF (Low Smoke and Fume) or RP (Reduced Propogation), when relating to signal or control cables will normally be modified PVC and produce 'Loads of Smoke and Fume'!