Echelon LonWork System Cabling
Designed for use on industrial and commercial bus systems,
these cables have become increasingly popular on Building Management Systems
(BMS). Available as one and two pair cables, screened and unscreened in
Low Smoke Halogen Free compounds they provide the ideal low cost solution
to BUS wiring.
1 & 2 Pair 22AWG I/O Cables for LonWork Systems
Unscreened Pairs
22(1)AWG plain copper conductors, foam PE insulation, cores twisted into
pairs,
Low Smoke Halogen Free sheath.
Technical Information
| Core Identification |
Pair 1: Blue/White, White/Blue |
| |
Pair 2: Orange/White, White/Orange |
| Operating temperature |
-5°C to +60°C |
| Conductor resistance |
53.0 Ω/km @ 20°C |
| Voltage |
Working : 300V |
| Velocity of propagation |
68% |
| Impedance |
100 Ω nominal |
| Capacitance, core to core |
45pF/m @ 1kHz |
| Attenuation |
MHz |
dB/100m |
| |
1 |
2.1 |
| |
4 |
4.2 |
| |
10 |
7.2 |
| |
20 |
10.0 |
|
|
|
Screened Pairs
22(1)AWG plain copper conductors, foam PE insulation, cores twisted into pairs,
overall foil and 22(1)AWG TCu drain wire, Low Smoke Halogen Free sheath.
Technical Information
| Core Identification |
Pair 1: Blue/White, White/Blue |
| |
Pair 2: Orange/White, White/Orange |
| Operating temperature |
-5°C to +60°C |
| Conductor resistance |
53.0 Ω/km @ 20°C |
| Voltage |
Working : 300V |
| Velocity of propagation |
68% |
| Impedance |
100 Ω nominal |
| Capacitance, core to core |
45pF/m @ 1kHz |
| core to screen |
80pF/m |
| Attenuation |
MHz |
dB/100m |
| |
1 |
2.1 |
| |
4 |
3.5 |
| |
10 |
5.6 |
| |
20 |
7.9 |
Technical Data |
Part
No. |
Belden
No. |
No.
of Pairs |
AWG
size |
Sheath
material |
Sheath
colour |
Weight
Kg/Km |
O/D
mm |
Screened |
|
2201PUGH |
7701NH |
1 |
22(1) |
LSHF |
White |
14 |
3.5 |
No |
|
2202PUGH |
7702NH |
2 |
22(1) |
LSHF |
White |
27 |
5.0 |
No |
|
2201POFGH |
7703NH |
1 |
22(1) |
LSHF |
White |
23 |
4.5 |
Yes |
|
2202POFGH |
7704NH |
2 |
22(1) |
LSHF |
White |
36 |
6.5 |
Yes |
|
| |
At FSC we refer to LSHF as Low Smoke Halogen Free
This term is interchangeable with LSZH (Low Smoke Zero
Halogen), LSOH (Low Smoke Zero Halogen), OHLS (Zero Halogen Low Smoke)
and FRNC (Flame Retardant Non-Corrosive). Beware of the terms LSF (Low
Smoke and Fume) or RP (Reduced Propogation), when relating to signal or
control cables will normally be modified PVC and produce 'Loads of Smoke
and Fume'!
Fire retardant, fire resistant, flame resistant or flame retardant?
These terms are often misunderstood. Most cables when
exposed to fire will not carry on functioning. If you require cable to
continue working in the event of fire, and in accordance with various
standards please call us. |
Some common mispellings of Belden Cable include - Beldon, Beldan, Balden, Baldon and Beldin.
|