BS 6724 LSHF Armoured Power Cables

Application

This cable is similar to BS 5467 but with the added advantage of Low Smoke Halogen Free properties making it ideal for use in tunnels, public buildings, airports and other applications where people and equipment are at risk in the event of fire.
     

Cable Construction

Plain copper wire conductors to BS 6360, class 2 (stranded), XLPE insulation, LSHF inner sheath, Galvanised Steel Wire Armour, LSHF sheath – Black.

Single core cables are supplied with an Aluminium Wire Armour (AWA) in accordance with BS6724.

Core Identification

Stock can be limited and minimum manufacture quantities may apply
2 Core Brown, blue
3 Core Brown, black, grey
4 Core Brown, black, grey, blue
5 Coreand above Brown, black, grey, blue, green/yellow
7 Core and above Number coded
Auxiliary type White cores with black numbers

Technical Information

Voltage rating 0.6/1kV
Conductors BS6360 class 2, circular, shaped or compacted.
Temperature rating 90°C maximum conductor temperature
Bending radius (static) 1.5mm² to 16mm²: 6 x overall diameter
  25mm² and above: 8 x overall diameter
Flame retardant IEC60332 part 3A, BS4066 part 3A
Design IEC60502-1 & BS 6724

Fire resistant versions to BS 6387 & IEC60331 are available, please contact us for details.

Technical Data - BS 6724 600/1000v cables with stranded copper conductor

Nominal cross-
sectional area
of conductor*
mm²
Thick-
ness of
insulation
mm
Diameter
under
armour
Nominal
aluminium
armour wire
diameter
mm
Thickness
of over-
sheath
mm
Approx.
overall
diameter
mm
Weight
kg/km

 Single core

 50   1.0  12.7  0.9  1.5  17.5  800
 70   1.1  14.7  1.25  1.5  20.2  940
 95   1.1  16.6  1.25  1.6  22.3  1220
 120   1.2  18.5  1.25  1.6  24.2  1490
 150   1.4  20.8  1.6  1.7  27.4  1870
 185   1.6  23.2  1.6  1.8  30.0  2290
 240   1.7  26.0  1.6  1.8  32.8  2880
 300   1.8  28.6  1.6  1.9  35.6  3520
 400   2.0  32.4  2.0  2.0  40.4  4520
 500   2.2  36.0  2.0  2.1  44.2  5680
 630   2.4  40.4  2.0  2.2  48.8  7120
Nominal cross-
sectional area
of conductor*
mm²
Thick-
ness of
insulation
mm
Diameter
under
armour
Nominal
steel
armour wire
diameter
mm
Thickness
of over-
sheath
mm
Approx.
overall
diameter
mm
Weight
kg/km

 2-core

 1.5*   0.7  7.7  0.9  1.4  12.3  305
 2.5*   0.7  9.0  0.9  1.4  13.6  352
 4*   0.7  10.1  0.9  1.4  14.7  419
 6*   0.7  11.3  0.9  1.4  15.9  498
 10*   0.7  13.2  0.9  1.5  18.0  764
 16*   0.7  14.5  1.25  1.5  20.0  900
 25*   0.9  18.4  1.25  1.6  24.1  1199
 25|   0.9  21.3  1.25  1.6  20.4  1000
 35*   0.9  19.0  1.6  1.7  27.9  1698
 35|   0.9  16.8  1.6  1.7  23.4  1490
 50#   1.0  19.0  1.6  1.8  25.8  1750
 70   1.1  22.0  1.6  1.9  29.0  2300
 95   1.1  25.1  2.0  2.0  33.1  3100
 120   1.2  27.9  2.0  2.1  36.1  3700
 150   1.4  30.9  2.0  2.2  39.3  4400
 185   1.6  34.9  2.5  2.4  44.7  5700
 240   1.7  39.0  2.5  2.5  49.0  7100
 300   1.8  43.3  2.5  2.6  53.5  8500

 3-core

 1.5*   0.7  8.2  0.9  1.4  12.8  338
 2.5*   0.7  9.5  0.9  1.4  14.1  397
 4*   0.7  10.7  0.9  1.4  15.3  481
 6*   0.7  12.0  0.9  1.4  16.6  639
 10*   0.7  14.0  1.25  1.5  19.5  908
 16*   0.7  15.5  1.25  1.6  21.2  1220
 25*   0.9  20.1  1.6  1.7  26.7  1702
 25|   0.9  17.0  1.6  1.7  23.6  1500
 35*   0.9  22.8  1.6  1.8  29.6  2120
 35|   0.9  19.1  1.6  1.8  25.9  1940
 50#   1.0  21.7  1.6  1.8  28.5  2225
 70   1.1  25.2  1.6  1.9  32.2  3025
 95   1.1  28.8  2.0  2.1  37.0  4275
 120   1.2  32.2  2.0  2.2  40.4  5250
 150   1.4  35.9  2.5  2.3  45.5  6650
 185   1.6  40.0  2.5  2.4  49.8  8045
 240   1.7  44.9  2.5  2.6  55.1  10150
Nominal cross-
sectional area
of conductor*
mm²
Thick-
ness of
insulation
mm
Diameter
under
armour
Nominal
steel
armour wire
diameter
mm
Thickness
of over-
sheath
mm
Approx.
overall
diameter
mm
Weight
kg/km

 4-core

 1.5*   0.7  8.9  0.9  1.4  13.5  381
 2.5*   0.7  10.4  0.9  1.4  15.0  452
 4*   0.7  11.8  0.9  1.4  16.4  563
 6*   0.7  13.2  1.25  1.5  18.7  795
 10*   0.7  15.6  1.25  1.5  21.1  1064
 16*   0.7  17.2  1.25  1.6  22.9  1410
 25*   0.9  22.3  1.6  1.7  28.9  2090
 25|   0.9  19.5  1.6  1.7  26.1  1950
 35*   0.9  25.3  1.6  1.8  32.1  2590
 35|   0.9  22.0  1.6  1.8  28.8  2350
 50#   1.0  25.0  1.6  1.9  32.0  2875
 70   1.1  29.2  2.0  2.1  37.7  4250
 95   1.1  33.3  2.0  2.2  41.7  5475
 120   1.2  37.5  2.5  2.3  47.1  7175
 150   1.4  41.6  2.5  2.4  51.4  8475
 185   1.6  46.4  2.5  2.6  56.6  10350
 240   1.7  52.6  2.5  2.7  63.0  13000
 300   1.8  58.0  2.5  2.9  68.8  15750

 5-core

 1.5*   0.6  10.6  0.9  1.35  15.1  426
 2.5*   0.7  12.5  0.9  1.4  17.1  549
 4.0*   0.7  14.2  1.25  1.5  19.7  810

 7-core

 1.5*   0.6  10.9  0.9  1.4  15.9  490
 2.5*   0.7  12.1  0.9  1.4  16.3  600
 4.0*   0.7  13.9  0.9  1.5  19.7  950

 12-core

 1.5*   0.6  13.9  1.25  1.5  19.4  817
 2.5*   0.7  16.7  1.25  1.55  22.3  910
 4.0*   0.7  19.3  1.6  1.55  25.6  1400

 19-core

 1.5*   0.6  16.5  1.25  1.65  22.3  1225
 2.5*   0.7  20.0  1.6  1.7  26.6  1500
 4.0*   0.7  22.7  1.6  1.75  29.4  1852

 27-core

 1.5*   0.6  20.1  1.6  1.65  26.6  1553
 2.5*   0.7  23.9  1.6  1.75  30.6  1928
 4.0*   0.7  27.4  1.6  1.9  34.4  2630

 37-core

 1.5*   0.6  22.4  1.6  1.5  29.2  1859
 2.5*   0.7  27.0  1.6  1.8  33.8  2360
 4.0*   0.7  31.2  1.6  2.45  39.3  3470
* Circular or compacted circular stranded conductors (class 2)
| Shaped stranded conductor (class 2)
# Cables having conductors of nominal cross-sectional area 50mm² and above have shaped stranded conductors (class 2)
Other conductor sizes available upon request