Application
Used for power and control circuits, these cables offer
excellent protection through the use of a heavy galvanised steel wire
armour. The GSWA makes them suitable for use inside and outside buildings
or for direct burial in the ground. |
|
Cable Construction
Plain copper wire conductors to BS 6360, class 2 (stranded),
XLPE insulation, PVC inner sheath, Galvanised Steel Wire Armour, PVC sheath
– Black.
Single core cables are supplied with an Aluminium Wire Armour (AWA) in accordance with BS5467.
|
|
Core Identification
| 2 Core |
Brown, blue |
| 3 Core |
Brown, black, grey |
| 4 Core |
Brown, black, grey, blue |
| 5 Coreand above |
Brown, black, grey, blue, green/yellow |
| 7 Core and above |
Number coded |
| Auxiliary type |
White cores with black numbers |
Technical Information
| Voltage rating |
0.6/1kV |
| Conductors |
BS6360 class 2, circular, shaped
or compacted. |
| Temperature rating |
90°C maximum conductor temperature |
| Bending radius (static) |
1.5mm² to 16mm²:
6 x overall diameter |
| |
25mm² and above: 8 x overall diameter |
| Flame retardant |
IEC60332 part 1, BS4066 part 1 |
| Design |
IEC60502-1 & BS 5467 |
|
Fire resistant versions to BS 6387 & IEC60331 are available,
please contact us for details. |
|