1. Home
  2. Data
  3. Bus Cables
  4. Interbus Cable

Interbus Cable

The Interbus open ring topology allows integration of different field devices from control level down to sensor switches over one system. Unlike traditional ring systems Interbus uses one cable to route data back and forth to all devices. Each device or unit will amplify the signal before sending it on to the next station. The data is transmitted over a 3 pair screened cable.  For remote applications a composite data and power cable is available.

Construction - Three Pair + Power

Data Cores

Plain copper conductors 0.22mm², PE insulated & twisted into pairs.

Power Cores

Plain copper conductors 1.0mm² PE insulation.

Cores and pairs bunched together, polyester tape, copper wire braid, PUR sheath.

Construction - Three Pair

Plain copper conductors 0.22mm², PE insulation, cores twisted into pairs, pairs bunched and polyester taped, copper wire braid, PVC sheath on static cables and a PUR sheath on dynamic cables.

Technical Information

Voltage Rating:300V
Temperature
Rating:
 
Flexing:-30°C +70°C
Static:-5°C +50°C
Velocity of
Propagation:
66% (Data Pairs)
Capacitance: 
Core to shield:51pF/m
Nominal
Impedance:
100 Ohms
Colour Code: 
Pairs:Brown/white, green/yellow, pink/grey
Cores:Red, blue, green
Hover Over Image to Enlarge
Print this page
Part No.Alt. to BeldenPairs x mm²Sheath MaterialO/D mmWeight Kg/KmApplicationScreened
2403/3POBP-HF3119A3 x 2 x 0.22mm² & 3 x 1.0mm²PUR9.385.00Dynamic with remote powerCFS-TCWB
2403POBP 3P x 0.22PVC8.072.00StaticCFS-TCWB
2403POBP-HF 3P x 0.22PUR8.272.00DynamicCFS-TCWB